113 Volts: Is It Too Low?

Last reviewed on 1 October 2026.

113 V at a North American outlet is low but normally acceptable: it is 5.8% below the 120 V nominal and above the roughly 110 V minimum that the ANSI C84.1 standard allows at the point of use. Measured at the meter (service entrance), though, the normal range starts at 114 V, so a steady 113 V there is slightly low and worth reporting to your utility. Appliances will work; heaters give about 11% less heat.

Electrical safety

113 V is ordinary mains voltage and can kill. This page is general information only. Switch off the circuit before touching wiring and use a licensed electrician for any electrical work.

Is 113 V Within the Standard? (ANSI C84.1)

In the US, ANSI C84.1 sets voltage ranges for 120 V systems. Range A is the normal design range; Range B allows occasional excursions that the utility should correct.

Where measuredRange A (normal)Range B (tolerable, occasional)Is 113 V OK?
Service entrance (meter)114–126 V (±5%)110–127 VSlightly below Range A, within Range B
Utilization (outlet / equipment)about 110–126 Vabout 106–127 VYes, within Range A

Minimum utilization voltages are a little lower (about 108 V in Range A) on circuits that do not supply lighting. Your utility's own tariff may state its exact service range.

Put simply: a reading of 113 V at a wall outlet, especially with appliances running, is within the normal allowance because some voltage is always lost in the building wiring. A reading of 113 V at the meter with little load in the house means the supply itself is on the low side.

How to Check Your Voltage Properly

  1. Measure with no big loads running using a multimeter set to AC volts or a plug-in voltage monitor.
  2. Measure again with a large load on (for example a 1,500 W heater or kettle on the same circuit). A drop of a few volts is normal.
  3. Compare outlets on different circuits. One low circuit points to wiring; every outlet low points to the supply.
  4. Log it over a day. Voltage often dips at peak demand times and recovers overnight.

As a guide, the US National Electrical Code's informational notes suggest designing for no more than 3% voltage drop on a branch circuit and 5% overall. A much bigger drop under load suggests undersized wire or a poor connection.

Why You Might Read 113 V

  • Voltage drop in wiring: long runs or thin wire between the panel and the outlet.
  • Heavy load: large appliances running on the same circuit, or high demand in the neighbourhood.
  • Supply setting: the utility transformer or regulator may be delivering the low end of the range.
  • Loose or corroded connections: at outlets, splices, the panel or the neutral. These cause drops that worsen under load and can overheat, so they need an electrician.

What 113 V Does to Appliances

Type of deviceEffect at 113 V vs 120 V
Resistive heaters, kettles, toasters, incandescent bulbsPower falls with voltage squared: (113/120)² = 0.887, so about 11.3% less heat or light. A 1,500 W heater gives about 1,330 W.
Motors (fridges, AC compressors, pumps)Usually fine; under load they draw a little more current and run slightly warmer. Very low voltage can stop compressors starting.
Electronics with switch-mode supplies (phones, laptops, TVs, LED lamps)No noticeable effect; most accept anything from about 100 to 240 V.

113 V Power Calculations

Formulas: P = V × I, I = V ÷ R, P = V² ÷ R.

  • 1 A at 113 V = 113 W
  • A 15 A circuit at 113 V can carry up to 1,695 W (2,260 W on a 20 A circuit)
  • A 100 Ω resistive load at 113 V uses 127.7 W (144 W at 120 V)
  • A device that needs a constant 1,200 W draws 10.6 A at 113 V instead of 10.0 A at 120 V

113 Volts Power Calculator

Calculate power, current or resistance at 113 volts:

Power = ? watts

113 V Around the World

SystemNominal voltageWhat 113 V means
US, Canada, Mexico (household)120 V, 60 Hz5.8% low; normally acceptable at the outlet
Japan100 V (50 Hz east, 60 Hz west)13% high; above Japan's usual tolerance
Europe, UK, most of Asia, Africa, Australia230 V, 50 HzLess than half of nominal: a fault, or a 115 V site/tool supply

"110 V" and "115 V" are older or informal names for the same North American 120 V supply, so a device labelled 110 V, 115 V or 120 V will run normally at 113 V.

Is 113 Volts Dangerous?

Yes. Voltages above the 50 V AC extra-low-voltage limit can drive harmful current through the body. How much depends on resistance: with wet skin it can be around 1,000 Ω, which at 113 V allows about 113 mA.

Approximate current (60 Hz AC)Typical effect
about 1 mABarely perceptible tingle
about 5 mANoticeable shock; GFCI outlets trip at around this level
about 6–30 mAPainful; may be unable to let go
about 50–150 mASevere pain, breathing can stop, ventricular fibrillation and death possible
about 1 A and aboveVentricular fibrillation likely, severe burns

Effects vary with current path, duration and the person. Use GFCI protection in kitchens, bathrooms and outdoors.

Frequently Asked Questions

Is 113 volts too low for a 120 V outlet?

Usually not. 113 V is 5.8% below the 120 V nominal. ANSI C84.1 allows about 110 V at the equipment (outlet) in its normal Range A, so 113 V at an outlet is acceptable. At the service entrance (the meter), Range A starts at 114 V, so a steady 113 V there is slightly low and worth reporting to your utility.

Can I use a 120 V appliance at 113 V?

Yes. Most 120 V appliances are designed to work across the ANSI range. Heaters, kettles and toasters deliver about 11% less heat at 113 V, motors run with slightly less torque and draw a little more current under load, and electronics with switch-mode power supplies are unaffected.

When should I worry about low voltage?

Call your utility or a licensed electrician if outlets read below about 110 V, if voltage drops sharply when a large appliance starts, if lights flicker or dim, or if outlets, plugs or the panel feel warm or smell hot. Large drops under load can point to a loose or corroded connection, which is a fire risk.

Is 113 volts dangerous?

Yes. 113 V is ordinary mains voltage and can cause a fatal shock. With wet skin the body's resistance can be around 1,000 ohms, which at 113 V would allow about 113 mA, enough to cause ventricular fibrillation. Always switch off the circuit before working on it.